AHU Economizer Configuration User Guide:

Importing Master Driver Configuration Store

At the initial homepage, the user will be prompted to upload the Master Driver file. Values within the Master Driver Configuration Store will be parsed to provide options for Campus, Buidling, Device and Points throughout the application.

_images/ahu_Frontpage.JPG

Once the user has selected the Master Driver Configuration Store, this homepage will not appear again. However, if the user needs to upload a different Master Driver Configuration Store at any point, this option can be accessed via the Menu icon in the top left of the application.

Warning

Uploading a new Master Driver Configuration Store will remove all current data in the application.

_images/master_Driver.jpg

After a Master Driver File is uploaded, there will be two new buttons that will appear as green below.

Below The Master Driver button, there are two buttons that say: AHU File and Generate configuration file for… The Ahu File will allow the user to submit a file that has been created by the AHU config previously, and the Generate configuration file for… will allow the user to create a new configuration file for either the ECONOMIZER or AIRSIDE.

_images/ahu_File.JPG

Economizer

This section will go over all of the items that are located within the Economizer button located in the Generate configuration file for… button.

When the Economizer is selected there will be a prompt to select Campus, Building, and Device. These will all be selected as dropdown inputs.

_images/dropdowns.JPG

AHU Application Configuration

The AHU Application behavior is controlled through these configuration Pages:

  1. Point Mapping
  2. Settings
  3. Thresholds

Point Mapping

Point Mapping will be the first tab on the left side of the Economizer page. This will be located underneath the main configuration file and the Default Economizer.

_images/point_Mapping.JPG

Once Point Mapping is selected, configurations will show on the center of the screen.

_images/point_Config.JPG

Once the configuration is shown in the center of the screen, the dropdown inputs may be selected to configure.

All of the Point Mapping configuration settings will be drop down inputs that are dependant Upon the main configuration file selected for the page.

_images/point_Populate.JPG

JSON

Throughout the AHU application, there is a page on the right hand side of the screen with visual accessibility of the JSON code. As items are input into the tab sections of the application the JSON code will populate with its corresponding items.

For Example: When a Device(s) is chosen on on the first page, the JSON code will populate with those same chosen devices.

JSON Example: At the start of the Economizer page when the user is prompted to input a Device, there is 5 options to choose from:

_images/device_Select.JPG

After the device is chosen there will be a dropdown of devices to choose from.

_images/ahu_Device.JPG

As these devices are chosen, they will be stored within the Json code on the right side of the page as items are selected.

_images/json_Econ.JPG

Settings

Settings is the second tab inside of the Ahu configuration Economizer section. Once settings is selected the center section will populate with configurations.

_images/settings.JPG

Device Type

Device Type will give you an option to either choose AHU or RTU underneath the settings title.

_images/device_Type.JPG

Economizer Type

Economizer type has two selections: DDB and HL. Choosing one will provide specific configuration settings.

_images/economizer_Type.JPG

Economizer Type: DDB

Data Window

This selection will be an integer type ranging from 0 to 60 minutes. The user may input an integer or use the slider to obtain the number required.

_images/data_Window.JPG

Numbered Required Data

This selection will be an integer type ranging from 0 to 20. The user may input an integer or use the slider to obtain the number required.

_images/number_Data.JPG

Desired Outdoor Air Fraction

This selection will be an integer type ranging from 5 to 30. The user may input an integer or use the slider to obtain the number required.

_images/desired_Outdoor.JPG

Open Damper Time

This selection will be an integer type ranging from 0 to 60 minutes. The user may input an integer or use the slider to obtain the number required.

_images/open_Damper.JPG

Minimum Damper Setpoint

This selection will be an integer type ranging from 0 to 50 %. The user may input an integer or use the slider to obtain the number required.

_images/minimum_Damp.JPG

Rated Cubic Feet Per Minute

This selection will be an integer type ranging from 0 to 6000 CFM. The user may input an integer or use the slider to obtain the number required.

_images/rated_Min.JPG

Energy Efficient Ratio

This selection will be an integer type ranging from 1 to 15. The user may input an integer or use the slider to obtain the number required.

_images/energy_Ratio.JPG

Temperature Deadband

This selection will be a floating point number ranging from 0.5 to 10. The user may also input a floating point number or use the slider to obtain the number required.

_images/temperature_Dead.JPG

Economizer type: HL

The Economizer type HL will be the next selection. Once this option is selected, there will be new settings that the user may configure.

_images/econ_Typehl.JPG

Economizer Switchover Setpoint

This selection will be a integer number ranging from 0 to 20. The user may input an integer or use the slider to obtain the number required.

_images/switch_Over.JPG

Data window

This selection will be a floating point number ranging from 0 to 60 minutes. The user may input an integer or use the slider to obtain the number required. .. image:: _images/data_Win.JPG

Number Required Data

This selection will be a floating point number ranging from 0 to 60 minutes. The user may input an integer or use the slider to obtain the number required.

_images/number_Req.JPG

Desired Outdoor Air Fraction

This selection will be a floating point number ranging from 5 to 30. The user may input a floating point number or use the slider to obtain the number required.

_images/desire_Frac.JPG

Open Damper Time

This selection will be a floating point number ranging from 0 to 60 minutes. The user may input an integer or use the slider to obtain the number required.

_images/damp_Time.JPG

Minimum Damper Setpoint

This selection will be a floating point number ranging from 0 to 50%. The user may input an integer or use the slider to obtain the number required.

_images/min_Damp.JPG

Rated Cubic Feet Per Minute

This selection will be a floating point number ranging from 0 to 6000 CFM. The user may input an integer or use the slider to obtain the number required.

_images/rated_Feet.JPG

Energy Efficient Ratio

This selection will be a floating point number ranging from 1 to 15. The user may input an integer or use the slider to obtain the number required.

_images/energy_Ratio2.JPG

Temperature Deadband

This selection will be a floating point number ranging from 1 to 15. The user may input an integer or use the slider to obtain the number required.

_images/Temp_Dead.JPG

Thresholds

The last tab in the AHU config: Economizer is the Threshold tab.

_images/sidepanel.JPG

Once this tab is selected, there will be two options that appear on the center of the screen.

_images/thres_Select.JPG

If Use Default thresholds* is selected, there will be no options to configure.

If Customize Threshold Parameters is selected, there will be new settings to configure.

_images/custom_Thres.JPG

Low Supply Fan

This selection will be a floating point number ranging from 0 to 100%. The user may input an integer or use the slider to obtain the number required.

_images/low_Sup.JPG

Mixed-Air Temperature Low

This selection will be a floating point number ranging from 40 to 60 degrees. The user may input an integer or use the slider to obtain the number required.

_images/mix_Temp.JPG

Mixed-Air Temperature High

This selection will be a floating point number ranging from 80 to 90 degrees. The user may input an integer or use the slider to obtain the number required.

_images/mix_Temp.JPG

Outside-Air Temperature Low

This selection will be a floating point number ranging from 20 to 40 degrees. The user may input an integer or use the slider to obtain the number required.

_images/out_Low.JPG

Outside-Air Temperature High

This selection will be a floating point number ranging from 90 to 125 degrees. The user may input an integer or use the slider to obtain the number required.

_images/out_High.JPG

Return-Air Temperature Low

This selection will be a floating point number ranging from 40 to 60 degrees. The user may input an integer or use the slider to obtain the number required.

_images/return_Low.JPG

Return-Air Temperature High

This selection will be a floating point number ranging from 80 to 90 degrees. The user may input an integer or use the slider to obtain the number required.

_images/return_High.JPG

Temperature Difference Threshold

This selection will be a floating point number ranging from 2 to 6. The user may input an integer or use the slider to obtain the number required.

_images/temp_Diff.JPG

Open Damper Threshold

This selection will be a floating point number ranging from 60 to 90. The user may input an integer or use the slider to obtain the number required.

_images/open_Damp.JPG

OAF Temperature Threshold

This selection will be a floating point number ranging from 5 to 15. The user may input an integer or use the slider to obtain the number required.

_images/oaf.JPG

Cooling enabled Threshold

This selection will be a floating point number ranging from 5 to 50. The user may input an integer or use the slider to obtain the number required.

_images/cooling_T.JPG

Saving Files

Once everything within the Economizer is configured, the last option will be to save the AHU file.

_images/save_As.JPG

Once the Save as button is selected, a new input will appear in the center of the screen.

_images/save_Ascust.JPG

This will allow the user to name the file whatever is desired. The file will automatically create the file as a .json file as well.

Once the save button is chosen, it will download to the browser as the file it was named.

_images/ahu_Filejson.JPG